Parameter |
Reference |
|
AC Current |
3/30mA, 30/60A |
|
Frequency Characteristics |
50/60Hz |
|
Accuracy |
50/60Hz |
1.0+5 (0~30mA)
1.0+5 (0 ~ 50A)
5.0+5 (50/60Hz) |
|
|
Parameter |
Specification |
|
Method of Detection |
Mean Value |
|
Diameter of Measurable conductor |
Ø40MM at maximum |
|
Display |
LCD |
Digital Display: 3200 Counts |
|
Bar-graph Display: 32 Segments |
|
Measurement Cycle |
Digital Display: 2 times/Seconds |
|
Bar-Graph Display: 12 times/second |
|
Range Switching |
Auto-Range |
|
Data Hold |
On All range |
|
Ambient Temperature and Humidity |
0-50˚C, 85% RH or less (no condensation) |
|
Temperature coefficient |
0.05% of range/°C or less (within the
ranges of 0-18°C and 25-50°C for measurement of 0-50A) |
|
Influence of external Magnetic Field |
0.0005% typical*1 (on current value of
adjacent cable) |
|
Influence of Conductor Position |
Within Accuracy |
|
Circuit Voltage |
300Vrms or less |
|
Withstanding Voltage |
3.7kV AC for one minute |
|
Power Supply |
CR2032 (coin-shaped) 3V x1 |
|
Battery Life |
Approx. 90 hours (continuous use) |
|
Auto Power-off |
Approx. 10 Minutes |
|
Dimensions |
Approx. 70(W)x176(H)x25(D)mm |
|
Weight |
Approx. 200g |