HOME > SEAWARD > HIPOT-TESTERS > CLAREHAL104 seaward logo

Seaward ClareHAL 104
Advanced Multi-Function Safety Tester
Discontinued

  • Automatic test sequences and configurations
  • Internal memory
  • Intuitive user interface
  • AC and DC Flash/Hipot
  • DC Insulation Resistance
  • ARC Detection
  • Earth/Ground Bond
  • Results Memory
  • Leakage Testing
  • Load Current Testing
  • Power Factor
  • Automation Option
  • Barcode scanner/printer Option
Click here for a larger image - Seaward H104Click here for a larger image
Seaward H104 Shown

Product Information
Datasheet 2.56 MB PDF
Click here for Information Regarding PDF'sPDF Help
 
The new ClareHAL 104 takes the features of previous ClareHAL versions and combines them into one easy unit. The ClareHAL 104 truly is the one size fits all solution - combined with results storage! The simple intuitive user interface enables easy push-button manual testing, alternatively the full power of this unique instrument can be used to automate the testing sequest for fast performance on the most demanding production lines.

The Clare HAL H104 is designed for simple manual testing and automatic mode for large volume applications in the most demanding environments. It is designed for use in manufacturing, laboratory, maintenance and high speed production environments either as a stand-alone test instrument or as an integrated part of a production line system.

Technically the Clare HAL H104 has isolated floating test outputs making it probably the safest hipot/dielectric tester on the market. Careful consideration has been given to the user interface to enable it to be used manually within laboratory, audit and product compliance environments. Clever use of a barcode scanner will not only automate the production flow, but will enable the product to be linked directly into most ISO quality systems covering production, laboratory and audit usage.

Need to collect test results and prove traceability? The HAL H104 does that too. It will even barcode scan the equipment under test and produce result labels, making the whole test process accurate, efficient and fast. Up to 6000 tests can be stored internally, and software is available to enable download to PC for further analysis or SPC. Test sequences can be automatically configured using a barcode scanner and the tester can be fully controlled from a host device via RS232, or external PLC I/O ports making it ideal for system integration. Due to the high level of flexibility and truly innovative features, the Hal is ideally suited to integration into larger automated systems.

A large, clear, full graphic display presents information either in a numerical or analogue format. Tests can be started and stopped by simply pushing the large buttons on the front of the instrument or choose from a variety of pre-selected automated configurations, including remote PCs, PLCs or interlocks. The advanced electronic design allows the operator to select either 50 or 60 hertz HiPot and Ground Bond Testing, making the instrument truly international in its application. Features such as arc detection and the ability to set maximum and minimum thresholds all combine to enhance the quality of the testing process.

The fully comprehensive ClareHAL104 combines all the electrical safety tests with the functional testing of load leakage and power factor. These features are particularly beneficial to organizations where energy consumption and efficiency are becoming a more important aspect of a product’s design.
 
Specifications
AC Flash/Hipot Test
Programmable Voltage Range 0.10 kV-5.00 kV (10V/Step Resolution)
Frequency Independent of Supply 50 or 60 Hz
Voltage Display Range and Accuracy 0.10 kV-5.00kV ±1% ± 5 Counts
Voltage Display Resolution 0.01kV
Current Display Range and Accuracy 0.01mA-20.00mA ±1% ± 5 Counts
Current Display Resolution 0.01mA
Selectable Range of Pass/Fail Levels 0.01mA-20.00mA
Maximum Current Output 20.00mA @5kV
Maximum Current Output Optional Arc Detection 9 Levels
DC Flash/Hipot Test
Programmable Voltage Range 0.10 kV-6.00 kV (10V/Step Resolution)
Voltage Display Range and Accuracy 0.10 kV-6.00kV ±1% ± 5 Counts
Voltage Display Resolution 0.01kV
Current Display Range and Accuracy 0.01mA-10.00mA ±1% ± 5 Counts
Current Display Resolution 0.01mA
Selectable Range of Pass/Fail Levels 0.01mA-10.00mA
Maximum Current Output 10.00mA
Optional Arc Detection 9 Levels
 Insulation Resistance Test
DC Output Voltage 250, 500 or 1000V selectable
Display Range 0.01MΩ-500MΩ
Display Range / Accuracy 0.03MΩ - 350 MΩ ± 5% ± 5 Counts
Display Resolution 0.01MΩ
Pass/Fail Level 0.00MΩ-500.0MΩ
Earth/Ground Bond
Test Voltage Nominal 6VAC
Frequency 50 or 60 Hz (independent of supply)
Display Range and Accuracy 0-1500mΩ ±2% ±5 Counts
Display Resolution 1 mΩ
Current/Load Resistance/Time 5 A - 1000mΩ - Continuous
10 A - 500mΩ - Continuous
25 A - 200 mΩ - Continuous
30 A - 150 mΩ - 60 secs
40A - 100 mΩ - 60 secs
Settable Output Current Range 0.1A - 40.0A
Selectable Range of Pass/Fail Levels 0-1500 mΩ
Power and Leakage Test
Power Output Rating
Test Voltage 110V - 230V AC 20A nominal (Vin-Vout)
Maximum Power Output Up to 5.0kVA (dependant on mains supply rating)
Output Power Measurement
Display Range and Accuracy 0.02kVA-5.00kVA ±2% ±0.02kVA
Selectable Range of Pass/Fail Levels 0.001kVA-5.000kVA
Single Phase Power Factor Measurement
Display Range and Accuracy Ratio 0.000 -1.000 ± 0.030
Selectable Range of Pass/Fail Levels 0.000-1.000
Leakage Current Measurement
Display Range and Accuracy 0.10mA-20.00 mA ± 1% ±5 Counts
Display Resolution 0.01mA
Selectable Range of Pass/Fail Levels 0.01mA-20mA
Touch Current Measurement
Display Range and Accuracy 0.02mA - 5.00 mA ± 1% ±5 Counts
Display Resolution 0.01
Selectable Range of Pass/Fail Levels 0.02mA-5.00mA
 
Ordering Information
Model  Description Buy Online Price
H104 Seaward ClareHAL 104 Advanced Multi-Function Safety Tester  Discontinued
Included Accessories
 
  • 1 - Mains cord
  • 1 - Calibration certificate
  • 1 - Measuring leads with Kelvin Clips
  • 1 - User Manual
Included