| Specifications |
| Environment |
| Application field |
The instrument is intended for use in
high-voltage substations and industrial environments. |
| Operating Temperature |
0°C to +40°C (32°F to +104°F) |
| CE-marking |
| Safety standards |
EC 61010-1:2001 Incl. national dev. for US
and CA EN 61010-1:2001 |
| EMC standards |
EN 61326: 1997+A1:1998+A2:2001 |
| General |
| Mains voltage |
100 – 240 V AC, 0 / 60 Hz |
| Power consumption |
150 W |
| Protection |
Thermal cut-outs, automatic overload
protection |
| Display |
LCD |
| Measurement Section |
| Current measurement |
Display Range |
0.0 – 2999 A |
| Basic inaccuracy |
±(0. % of reading +0.2 A) |
| Resolution |
0.1 A |
| Internal current measurement |
Range |
0 – 270 A |
| Input for clamp-on ammeter |
Range |
0 – 1 V |
| mV/A-ratio |
Software settable, 0.3 to 19.9 mV/A |
| Input impedance |
>1 MΩ |
| Voltage measurement |
Display range 0.0 – 60 V |
Basic inaccuracy: ±(0. % of reading +0.1 V) Resolution:
0.1 V |
| Display range 0.0 – 500 V |
Basic inaccuracy: ±(0. % of reading +1 V) Resolution:
0.1 V |
| Time measurement |
Basic inaccuracy |
±0.1% of reading ±1 digit |
| Load Section |
| Battery voltage |
10 – 60 V DC |
| Max. current |
270 A |
| Max. power |
1 kW |
| Load patterns |
Constant current, constant power, constant
resistance, current or power profile |
| Current setting |
0-270.0 A (2999.9 A) |
| Power setting |
0-1 .00 kW (299.99 kW) |
| Resistance setting |
0.1-2999.8 Ω |
| Battery voltage range |
2 ranges, selected automatically at start of
test |
| Inputs, Maximal Values |
| External current measurement |
1 V DC, 300 V DC to ground. Current shunt
should be connected to the negative side of the battery |
| Start/stop |
Closing / opening contact Closing and then
opening the contact will start / stop Torkel. It is not possible
to keep the contacts in closed position. |
| Voltage sense |
60 V DC, 00 V DC to ground |
| Serial |
< 1 V |
| Alarm |
250 V DC 0.28 A 28 V DC 8 A 250 V AC 8
A |
| Outputs, maximal values |
| Start/Stop |
5V, 6 mA |
| TXL |
Relay contact |
| Serial |
< 15 V |
| Alarm |
Relay contact |