Specifications |
|
Input Power |
110 VAC |
± 15% or 12 to 15 VDC |
|
220 VAC |
± 15% or 12 to 15 VDC |
|
24 VAC |
± 15% or 12 to 15 VDC |
|
Current |
250 mA DC max. or 6.5 VA (6.5W) AC |
|
Inputs |
3: |
High Impedance DC pulse input 4-30 VDC
(high), Open or0-1 VDC (low), 10 kΩ impedance, 10 kHz max.
speed. |
|
3M: |
Mag. Input, accepts 30mV input (50 V max.)
signals 10 KΩimp. 5 kHz max. |
|
Temperature |
Operating |
+32°F (0°C) to +130 F (+54°C) |
|
Storage |
-40 F (-40°C) to +200°F (93°C) |
|
Memory |
EEPROM stores data for 10 years if power is
lost. |
|
Reset |
Front Panel: |
Resets displayed total value and control
output. |
|
Remote: |
4-30 VDC (75-240 V AC/DC, Input 8) negative
edge resets the A total and relay control output. |
|
Notes: |
The remote reset does not reset the grand
total. |
|
Memory |
EEPROM stores data for 10 years if power is
lost. |
|
Control Output |
Relays: |
2 each N.O. Relay; 5 Amps, 120/240 VAC or 28
VDC. (N.C.relay contacts and NPN transistor output available
via solder jumpers. |
|
Analog Output: |
An optional 4-20mA (0-20mA) output is
available for the Minitrol series. The output can be
programmed to track rate or total. This feature is available
by adding suffix A to the part number. Connections are via a
2 terminal pluggable screw connector. Programming is
accomplished by using the front panel in conjunction with
rear dip switches. |
|
Accuracy: ± 0.25% FS Compliance |
|
Voltage: 3 to 30 VDC non inductive. |
|
Presets |
Two control outputs are provided. To set
relay A or B's functionality, press "menu" button until
"Relay" appears on the display, the A and B outputs can be
assigned to the rate alarm (high/low), or for total/grand
total. A 5 digit value can be entered for both presets A and
B. The decimal point location is the same as the counter.
The outputs can be set to energize from 0.1 to 99.9 seconds
or latch (0.0). If a value other than 0.0 is entered, the
corresponding totalizer will auto reset at the preset. This
may be used to create a relay scaled pulse output. |
|
Option: RS232/RS422 |
If the serial interface option is supplied,
multiple units can be linked together. (The terminal
addressing the unit must be capable of driving all loads in
the loop.) Unit status and new set points can be
communicated by serial communication. Mode changes, however,
must always be made on the front panel.
Data is received and transmitted over standard EIA RS232or
RS422 levels. Unit number, baud rate and parity are entered
in the "Program Setting" set up mode and remain in memory
even if power is off. |
Option: RS232/RS422/RS485
with Modbus RTU Protocol |
The serial port can be used for serial
printing or also for data acquisition. The unit can assign
addresses up to 247 units (The terminal addressing the unit
must be capable of driving all loads in the loop.) The unit
can communicate with a master device through a Modbus-RTU
protocol. The data given for each parameter is in IEEE float
format comprising of 2 words. The unit can be connected in a
network.
Device ID: 01-247
Baud Rates: 300, 600, 1200, 2400, 4800, 9600
Parity: None, Odd, Even
Protocol: Modbus RTU (Half Duplex) |