General Specifications |
|
Operating Temperature |
32° F (0° C) to 158° F (70° C) |
|
High Level Pulse Input |
Type: |
Opto-Isolated |
|
Input Impedance: |
3.3 kΩ |
|
Logic 1: |
4-30 VDC |
|
Logic 0: |
0-1 VDC |
|
Frequency Range: |
0-10 kHz |
|
Fault Protection: |
Reverse Polarity Protection |
|
Over Voltage Protection |
|
Isolation Voltage: |
500 V |
|
Fast Transient Immunity: |
500 V |
|
Maximum Rise Time: |
No Limit |
|
Maximum Fall Time: |
No Limit |
|
Magnetic Pickup Input |
Input
Impedance: |
10 kΩ |
|
Frequency
Response: |
0-3500 Hz |
|
Trigger
Sensitivity: |
30 mV p-p |
|
Over
Voltage Protection: |
±30 VDC |
|
Contact Closure Input |
Sensor
Compatibility |
Requires an isolated, contact closure |
|
Maximum
Contact Voltage |
5 V |
|
Maximum
Contact Current |
0.12 mA |
|
Nominal
Pullup Resistance |
47 Kohm to 5 Vdc |
|
Frequency
Range |
0-100 Hz |
|
Frequency to current Conversion |
Standard |
150 Hz, 300 Hz, 600 Hz, 1200 Hz, 2500 Hz, 5000
Hz, 10,000 Hz
Factory Default: 1000 Hz |
|
Contact
Closure Option |
30 Hz, 60 Hz, 120 Hz, 240 Hz, 480 Hz, 960 Hz,
1920 Hz
Factory Default: 100 Hz |
|
Analog Output |
Accuracy: |
± 0.1% Span (@20° C) |
|
Output
Type: |
Two Wire, Loop Powered |
|
Range:
|
4-20 mA |
|
Compliance
Voltage: |
10 to 40 VDC |
|
Loop
Burden: |
< 10 VDC |
|
Time
Controls: |
Zero & Span, non-interacting |
|
Linearity: |
<± 0.002% Span/Volt |
|
Temperature
Effect: |
< 200 PPM/C° |
|
Noise
Content: |
< 0.2% Span |
|
Response
Time: |
0.1 second (1 sec. jumper selectable) |
|
Overcurrent
Limiting: |
35 mA |
|
Output
Loop Indicator: |
LED illuminates when output loop is powered by
proper polarity and blinks proportionally to the input frequency |
|