Specifications |
|
Display: |
4 1/2 digit, .55"
high, 7 segment, red orange, LED. |
|
Input Power: |
110, 220 VAC ± 15%
or 12 to 24 VDC.
Current: 300 max. mA DC or 10.0 VA (10W) at rated AC
voltage. |
|
Output Power: |
(AC powered units
only) + 24VDC @ 50mA regulated ±5%. (100 mA available on
request) |
|
Temperature: |
Operating: +32°F
(0°C) to +130°F (+54°C).
Storage: -40°F (-40°C) to +200°F (93°C). |
|
Memory: |
EEPROM stores data
for ten years if power is lost. |
|
Reset: |
Front Panel: resets
displayed value and control outputs. |
|
Control Outputs: |
Standard: Open
collector sinks 250mA from 30 VDC when active.
Optional: 2 each Form C SPDT 5 Amp @ 120/240 VAC or 28
VDC. |
|
Input: |
Linear 0-20mA,
4-20mA, 0-5V, 0-10V or 1-5V selectable from the front
panel. |
|
Calibration: |
The unit does all
of the calibrations internally. There are no
potentiometers to adjust and the unit never needs to be
removed from the case or panel. |
|
Set Points: |
Two control set
points are provided. The unit comes standard with two
open collector control outputs. Two 5 Amp, Form C relays
are optional. The outputs have a programmable alarm
range from -9999 to 49999 with hysteresis. |
|
Process Display: |
Updates 4 times per
second, Accurate to 4.5 digits. |
|
Programming: |
Decimal points,
Scaling from -9999 to 49999, set points, input type and
security lock code are all programmable from the front
panel. |
|
Housing: |
1/8 DIN, high
impact ABS plastic case (NEMA 4X/IP65 front panel). |
|
Overvoltage Protection: |
50 V |
|
Over-current Protection: |
50 mA |
|
Temperature Stability: |
Will not drift more
than 10 parts per million per °C from 0°C to 54°C |
|
Accuracy: |
.1% (5 V inputs
.16%) |
|
Listing: |
CE Compliant, CSA
(File No. LR91109),NRTL/C pending |