Specifications |
|
Supply Voltage |
10-30 VDC,
galvanically isolated with reverse polarity protection |
|
Current Draw: |
Max. 40 mA |
|
Display: |
5-digit display,
red 7-segment LED's; height 8 mm |
|
Measuring Rate: |
5
measurements/second |
|
Display Refresh: |
1-2 times per
second |
|
Data Backup: |
EEPROM |
|
Housing: |
Housing for control
panel 48 x 24 mm acc. to DIN 43 700; RAL 7021, dark grey |
|
Ambient Temp.: |
-20 to +65° C |
|
EMC: |
according to EC EMC
directive 89/36/EEC |
|
Interference Emissions: |
EN 500081-2/EN 55
011 Class B |
|
Protection: |
NEMA4 / IP65
(front) |
|
Input: |
Thermocouple Sensor
J (FE-CuNi)
K (Ni-CrNi)
N (NiCRSi-NiSi)
with sensor breakage monitoring |
|
Control Inputs: |
High: 4-30 VDC,
Low: 0-2 VDC |
|
Supply Currents: |
1 mA |
|
Supply Line: |
2-wire: max 20
Ω, programmable 3-wire,
4-wire: max 20
Ω, no balancing required |
|
Temp. Ranges: |
J (Fe-CuNi):
210.0°C to +1200.0°C
346.0°F to +2192.0°F |
K (Ni-CrNi):
200.0°C to +1372.0°C
328.0°F to +2501.6°F |
N (NiCrSi-NiSi):
200.0°C to +1300.0°C
328.0°F to +2370.0°F |
|
Resolution: |
0.1°C (0.1°F) or
1°C (1°F) |
|
Linearity Error: |
< 0.4% for entire
measuring range at an ambient temperature of 20°C |
|
Cold Junction Error: |
±0.1°C typ. ±3.0°C |
|
Temp. Drift: |
0.1 K/K Ambient |