Phone 800-517-8431
Click for larger imageEagle Eye IPQMS-C64 Battery Monitoring System for 0-120 VDC Systems using 1.2-12V Batteries


Eagle Eye IPQMS-C64 Battery Monitoring System for 0-120 VDC Systems using 1.2-12V Batteries

Model No: IPQMS-C64
Our Model No: IPQMSC64
Condition: NEW
PDF Document Icon Data Sheet (1.1 MB)
Sale $9,360.00

Product Features:

  • Utilizes patented technology to identify & alarm the user of early signs of battery deterioration to ensure the integrity of your critical back-up batteries.
  • Adopting the world�s first ripple-removing algorithm, USA patent: US 7,567,085B2, the system precisely measures battery health while the system is on-line.
  • With flexible expanding solutions, BMS/i-com can monitor ALL your systems in real time.
  • Complete with battery management software to allow monitoring 24 hours a day, 365 days a year via a remote computer(s).
  • In the event a voltage sag, power failure or alarm occurs, the event is transmitted to the administrator via SMS through a remote communication device.
  • Software package allows for the most comprehensive battery system diagnosis and reporting capabilities.
  • IPQMS meets all IEEE standard recommendations for battery monitoring

Eagle Eye's iPQMS-C64 Battery Monitoring System is designed to measure the aging status of up to 448 jars (or 448 cells) by measuring and recording: string voltage,DC current, jar/cell voltage, internal resistance (I.R.), connection resistance, and temperature. The iPQMSC64 is designed for use on vented lead acid, valve regulated lead acid, and nickel-cadmium battery systems. The included Centroid Snet Battery Management Software records measured data for comprehensive trending analysis, ensuring backup power systems are optimally maintained. The iPQMS-C64 system measures up to 448 jars (or 448 cells) through clamps connected directly to the battery connections. The iPQMS-C64 can be used on a private network via TCP/IP or locally with direct RS-232 connection. Networked systems can utilize SMS/Email alerts during alarm outbreak. Modbus protocol can be utilized for third-party software integration.

  • 1 - Centroid Snet Battery
  • 1 - Management Software
  • 1 - iPQMS MPU with mounting kit
  • 1 - Relaying Unit(s)
  • 1 - O-Clamps for inter-cell cable connections
  • 1 - C-Clamps for inter-cell busbar connections
  • 1 - Cabling for string voltage measurement
  • 1 - Cabling for cell voltage, cell I.R. and temp. measurement
  • 1 - CT clamp for DC current measurement
  • 1 - Power cabling
  • 1 - Optional: Spare parts kit
Datasheet: PDF Document Icon(1.1 MB)