<< Amprobe Megohmmeters/Insulation
Testers
|
- Tests insulation of wires, cables, transformers and electrical
motors
- Comes as a complete kit including test leads and PC software
- Selectable test voltages 250V, 500V and 1000V
- Programmable timer to perform the Dielectric Absorption Ratio
Test
- Sensitive Ohmmeter for checking resistance of motor windings
- Selectable polarization of ohmmeter for checking grounding
continuity
- Automatic voltmeter warns against hazardous energized systems
- Fast and easy to use, rugged durable design
- Internal memory to store measurements for future reference
- Data download to PC
|
 
Amprobe AMB-6D Shown
|
|
|
|
Specifications |
|
Continuity |
|
Test Mode |
Measuring Range (Ω) |
Resolution (Ω) |
Accuracy |
|
AUTO, R+, R |
0.01 - 19.99 |
0.01 |
±(2% reading+ 2 digits) |
|
20.0 - 99.9 |
0.1 |
|
R+ Timer, R- Timer |
0.01 - 9.99 |
0.01 |
|
Test Current |
>200mA DC up to 16Ω (includes the
Resistance of the calibration) 40mA DC from 16Ω to 99.9Ω |
|
Test Current
Resolution |
1mA |
|
Open Circuit Test
Voltage |
9V |
|
Insulation
Resistance |
|
Test Voltage (Ω) |
Measuring Range (Ω) |
Resolution (Ω) |
Accuracy |
|
50 |
0.01 - 19.99 |
0.01 |
±(2% reading+ 2 digits) |
|
20.0 - 49.9 |
0.1 |
|
50.0 - 99.99 |
±(5% reading+ 2 digits) |
|
100 |
0.01 - 19.99 |
0.01 |
±(2% reading+ 2 digits) |
|
20.0 - 99.9 |
0.1 |
|
100.0 - 199.99 |
±(5% reading+ 2 digits) |
|
250 |
0.01 - 19.99 |
0.01 |
±(2% reading+ 2 digits) |
|
20.0 - 199.9 |
0.1 |
|
200.0 - 249 |
1 |
|
250 - 499 |
±(5% reading+ 2 digits) |
|
500 |
0.01 - 19.99 |
0.01 |
±(2% reading+ 2 digits) |
|
20.0 - 199.9 |
0.1 |
|
200.0 - 499 |
1 |
|
500 - 999 |
±(5% reading+ 2 digits) |
|
1000 |
0.01 - 19.99 |
0.01 |
±(2% reading+ 2 digits) |
|
20.0 - 199.9 |
0.1 |
|
200.0 - 999 |
1 |
|
1000 - 1999 |
±(5% reading+ 2 digits) |
|
Automatic Selection
of the Measuring Range |
|
Open Circuit Voltage
|
1, 1 x Rated Voltage Test |
|
Short Circuit Current
|
<3.0 mA - 500V
<2.0 mA - 50V, 100V, 250V, 1000V |
|
Rated Measuring
Current |
2.17 mA - 500V/230kΩ
1mA - 1000V/1MΩ |
|
Additional Notes
|
If the Instrument measures a voltage
higher than 30V, the instrument will not take a measurement |
|
Safety Standards |
|
Insulation |
Class 2, Double insulation |
|
Over-voltage Category |
CATIII |
|
Environmental
Conditions |
|
Reference Temperature |
73°F (23°C) |
|
Operating Temperature |
14 - 140°F (-10 - 50°C) |
|
Storage Temperature |
68 - 140°F (20 - 50°C) |
Permitted Relative
Humidity
(Operating Temp.) |
<80% |
|
Storage Humidity |
<70% |
|
|
|