Specifications |
Range |
Accuracy |
|
100 <
500V |
500V
< 1000V |
1000V
< 2500V |
2500V
< 5000V |
|
Insulation Resistance |
Insulation
Measurement |
100K - 500K |
±(20% + 10 dgt) |
|
500K + 50G |
±(5% + 1 dgt) |
|
50G - 100G |
±(20% + 10 dgt) |
±(5% + 1 dgt) |
|
100G - 250G |
--- |
±(20% + 10 dgt) |
±(5% + 1 dgt) |
|
250G - 500G |
--- |
±(20% + 10 dgt) |
±(5% + 1 dgt) |
|
Minimum Resistance
Resolution |
1% |
Voltage Indication
Resolution |
1.22V |
|
Amount of Current
Delivered |
Voltage Setting |
100 - 500V |
|
1000 - 5000V |
|
Max Current |
3.00 mA |
|
1.40 mA |
|
Voltage Measurement |
Voltage Range |
0 - 500V |
|
500 - 5000V |
|
Resolution |
1.22V |
|
Accuracy |
0 - 500V: ±(10% + 10 dgt)
500 - 5000V: ±(10% + 5 dgt) |
|
Safety |
Instrumental
According to Standard |
EN 61010-1 |
|
Insulation |
Class 2, Double insulation |
|
Pollution Level |
2 |
|
Indoors use; max
Altitude |
6,562 Feet |
|
Over-Voltage Category |
CAT III 600V |
|
Serial Port
Insulation |
25 mm (Max: 5000V) |
|
General
Specifications |
|
Electric Features |
Measuring method |
Voltamperometric System |
|
Parameter memory |
20 different Parameters |
|
Stored measurements |
200 measurements with their parameters
and results |
|
RS232 |
DIN 9 Pin |
|
Power Supply |
Power Source |
4 "D" size 1.5volt Alkaline batteries |
|
Low Battery
Indication |
"Battery" symbol appears on the display |
|
Endurance |
250 measurement |
V= 5000V |
Rx = 5MΩ |
T = 1 Minute |
|
450 measurement |
V= 500V |
Rx = 500KΩ |
T = 1 Minute |
|
Automatic Turn Off |
Turns off after 10 Minutes without Use |
|
Ambient Conditions |
Temperature of
reference |
73°F +/- 1° (23°C +/- 1°) |
|
Operating Temperature
|
41 - 104°F (5 - 40°C) |
|
Storage Temperature |
11 - 140°F (-10 - 60°C) |
|
Permitted Relative
Humidity (Operating Temp.) |
<80% |
|
Storage Humidity |
<70% |
|
Noise Level |
< 40dB |
|
Display |
Features |
LCD 1 unit 3 Digits, 2 Units and 4
digits
Bargraph: 32 Segments + other Symbols |
|
Updating Speed |
Maximum of 2 seconds depends on the
value of the resistance being measured and on the stray capacitance
present in parallel. During the first 15 seconds the resistance
value is shown as "---" |
|
Dimension (LxWxH) |
290 x 340 x 145 mm
; (11.5 x 13 x 5.75 inches) |
|
Weight |
4 Kg (8.8 Lbs) |