<< ACR Catalog |
ACR PowerWatch
Voltage Disturbance Recorder
|
- Records essential voltage disturbance events:
- Surges
- Sags
- Outages
- Dropouts
- Impulses
- Frequency variations
- Records up to 4000 events
- 10-year battery life
- Safe, stand-alone operation
- No wires, alligator clips or other exposed wiring
- Hot-Neutral and Neutral-Ground monitoring
|
 
ACR PowerWatch Shown
|
|
|
|
Use the PowerWatch as your first line of defense against power
quality problems. Simply plug it into any power receptacle
(120-volt North American or 220/240-volt Australian, European or
UK) and begin monitoring and recording essential voltage
disturbance information-surges, sags, outages, impulses,
dropouts, and frequency variations. Set up your pre-determined
disturbance threshold values or use the industry standard
default values using PowerWatch software. No wiring or dangerous
connections are required. |
|
|
|
PowerWatch Specifications |
|
Memory Size: |
32 KB (4,000 events) |
|
Fuse: |
1/16A fast-blow (non-replaceable) |
|
Storage Methods: |
First-in, First-out then Fill then stop |
|
Sampling Methods: |
Continuous (half-cycle integrated) |
|
Alarm Type: |
Optical (flashing red LED) |
|
Measurement Specifications |
Surge, Sag
Outage
(120-volt version) |
Range: |
Hot to Neutral |
Neutral to Ground |
|
0 to 200 Vrms
|
3 to 200 V rme |
|
Accuracy: |
+/- 1 V rms
+ resolution |
+/-1 V rms
+ resolution |
|
Resolution: |
1 V rms |
1 V rms |
Surge, Sag
Outage
(220/240-volt version) |
Range: |
0 to 400 Vrms
|
3 to 200 V rme |
|
Accuracy: |
+/- 2 V rms
+ resolution |
+/- 1 V rms
+ resolution |
|
Resolution: |
2 V rms |
1 V rms |
|
Impulse: |
Range: |
100 to 2500 V Peak |
50 to 2500 V peak |
|
Accuracy: |
+/- 10% of reading
+ resolution |
+/- 10% of reading
+ resolution |
|
Resolution: |
10 V |
10 V |
|
Frequency: |
Range: |
45 to 65Hz |
|
Accuracy: |
+/- 0.1Hz (3 cycles minimum) |
|
Resolution: |
0.1Hz |
Time:
(Events <1 Second) |
Accuracy: |
+/- 0.5 Cycle |
+/- 1 cycle |
|
Resolution: |
0.5 Cycle |
1 Cycle |
Time-Stamp:
(>1 sec) |
Accuracy: |
+/- 2 sec/day + resolution |
|
Resolution: |
8 Seconds |
|
General Specifications |
|
Physical Dimensions: |
Case Material: |
Noryl plastic |
|
Size: |
85 mm x 68 mm x 35 mm (3.35" x 2.65" x 1.35") |
|
Battery: |
Type |
3.6 volt Lithium |
|
Life: |
10 Years under normal use |
|
|
Software/PC Requirements |
|
Processor/Operating System |
IBM PC or 100% compatible running WIndows
3.1, '95, '98, 2000, ME, NET, XP |
|
Available Hard drive space |
At Least 2MB |
|
Memory |
At Least 2MB |
|
Communication Ports |
1 Free Serial Port |
|
Software Requirements |
More info
on the PowerWatch Software Program>> |
|
|
|