| AEMC ML912 Specification |
| Electrical |
| Channels |
Two |
| Input |
Captive MiniFlex AC Current Flexible Sensors |
| Measurement Range |
0.5 to 100AAC and 5 to 1000AAC |
| Resolution |
0.1A |
| Accuracy |
0 to 1A Unspecified 1 to 100A ±(1% of Reading + 0.5A) 0 to 5A unspecified 5 to 1000A ±(1% of Reading + 1A) |
| Sample Rate |
64 samples/Cycle |
| Storage Rate |
Programmable from 125ms to 1 day |
| Record Length |
15 minutes to 8 weeks, programmable using DataView |
| Memory |
240,000 measurements (512KB) - The Recorded data is stored in non-volatile memory and will be retained even if the battery is low or removed. |
| Communication |
USB 2.0 Optically Isolated |
| Power Source |
2 x 1.5V AA-cell alkaline batteries |
| Battery Life |
100 hours to >45 days (dependent on sample rate and recording length) |
| Mechanical |
| Dimensions |
4.95 x 2.75 x 1.28" (136 x 70 x 32mm) w/o Sensor |
| Weight (with battery) |
8.67 oz (245g) with battery |
| Sensor/Cable Length |
Sensor: 6" (152mm) / Cable: 6 ft (2m) |
| Case |
UL94-VO |
| Vibration |
IEC 68-2-6 (1.5mm, 10 to 55Hz) |
| Shock |
IEC 68-2-27 (30G) |
| Drop |
IEC 68-2-32 (1m) |
| Environmental |
| Operating Temp. |
14° to 122°F (-10° to 50°C) |
| Storage Temp. |
-4° to 140°F (-20° to 60°C) |
| Relative Humidity |
Up to 85% at 95°F (35°C), Non-condensing |
| Altitude |
2000m |