<< AEMC Data LoggersAEMC CL601
Clamp-on Simple Logger II
|
- Self Contained, No Exposed Connections
- 0 To 600Arms Input
-
TRMS Measurements
- Easy-To-Use One Button Operation
-
Overload Indication
- Alarm Function
- Optically
Isolated USB 2.0
- Harmonics Are Only Available From The Simple
Logger II Control Panel Within The DataView Application
- 300V Cat. IV; 600V Cat. III
|

AEMC CL601 Shown
|
| |
|
The Simple Logger II Model CL601 is a battery powered, one channel recording
device with an alkaline battery pack. Line tracking is performed such
that 64 samples over one line cycle are taken. Frequency tracking is
performed over the range of ± 2Hz around the nominal line frequency
(50 or 60Hz). Harmonic measurements are calculated from these 64
samples. The CL601 Simple Logger II records TRMS at a rate of up to eight
times per second. The measurement process is performed no more than
eight times per second. TRMS calculations are performed on a single
line cycle. The main advantage of the CL601 is its ability to perform
a variety of recording tasks with easy and intuitive setup from a computer
using DataView Software |
|
|
|
Specifications |
| Channels |
1 |
| Input |
Split CT - AC Current |
| Resolution |
0.1A |
Accuracy
(50/60Hz) |
5 to 50A: ±(1% of Reading +1A) |
| 50 to 400A: ±(1% of Reading +0.5A) |
| 400 to 600A for duration <10min: ±(3% of
Reading +1A) |
| Sample Rate |
64 samples/cycle |
| Storage Rate |
Programmable from 125mS to 7 days |
| Storage Modes |
Start/Stop, FIFO and XRM |
| Recording Length |
1minute to 8 weeks, programmable using
DataView |
| Memory |
240,000 measurement (512KB) |
| Alarm |
Yes |
| Harmonics |
Yes - Up To The 50th |
| Waveforms |
Yes |
| Real-Time Trend Viewing |
Yes |
| Report Generation |
Configurable with DataView Software |
| Communication |
USB 2.0 |
| Communication Rate |
115200 bps |
| Power Source |
2x1.5V AA-Cell Alkaline Batteries |
| Battery Life |
100 hours to > 45 days |
|
|
|